RFC 0003: Writing to OT devices from the cloud — device parameters

Status: proposed — implemented as a working prototype alongside this RFC (SDK, CLI, flows, operations, e2e and cloud suites)

Reading OT points into the cloud is solved (samples → flows → measurements). Writing back is only half solved: the connector contract has a write verb and Cumulocity’s legacy c8y_SetRegister/c8y_SetCoil operations are shimmed onto it, but

  • those operations are Modbus-flavoured, need a per-protocol shim, and have no UI beyond a raw operation dialog;
  • an operator has no way to see the current value of a writable point next to the control that changes it;
  • nothing tells the cloud which points are editable, with which type and limits.

Cumulocity has a generic answer — device parameters: Digital Twin Manager (DTM) property definitions declare a parameter set as a JSON schema, the device reports the set’s current values as a fragment on its managed object (kept fresh through c8y_ParameterUpdate events), and edits in the device’s Parameters tab arrive as one c8y_ParameterUpdate operation per set. This RFC decides how tedge-dot plugs into that, and settles the four questions the feature raises.

Keep the connector a dumb, cloud-agnostic driver and bridge parameters in flows. The configuration already says which points are parameters (access = "read_write" / "write", optionally refined by meta.parameter); the runtime echoes each point’s access in its samples, so a single flow, ot-parameter-state, can publish the current values of every parameter as one retained twin fragment per parameter set (te/device/<device>///twin/<set>, keyed by point id) — that fragment is what a cloud UI displays and edits. The SDK runtime gains one protocol-neutral verb, write-batch, built on the module’s write, so an edit of several parameters is one command with one result; the existing command flows carry it (ot-command-forward reshapes an parameter_update command into a write-batch, ot-command-result completes it). The Cumulocity glue is one generic operation template (c8y_ParameterUpdate → parameter_update). The cloud-side declaration of the sets (Digital Twin Manager property definitions) is a tenant admin’s one-off act; tedge-dot describe prints it from the same TOML so the config remains the single source of truth, but the device never talks to the DTM service. Writes travel as thin-edge commands over MQTT, never through the tedge-dot write CLI.

1. Where does the DTM definition come from?

Section titled “1. Where does the DTM definition come from?”

From the connector configuration, rendered on demand for a tenant admin to register once:

Terminal window
# One definition per line, and the DTM service takes one per request — a configuration that
# groups its parameters (§5.2) renders several. `</dev/null` matters: without it c8y reads the
# loop's stdin as its own input pipeline and the remaining definitions are never registered.
defs=$(mktemp) one=$(mktemp)
trap 'rm -f "$defs" "$one"' EXIT
# every connector config the service runs (/etc/tedge/plugins/ot), a shared set rendered once
tedge-dot describe --compact > "$defs"
# Read from a file, not a pipe: a `while` on the right of a pipe runs in a subshell, where
# `exit 1` would abort only the loop and leave the script reporting success.
while read -r definition; do
printf '%s' "$definition" > "$one"
C8Y_SETTINGS_CI=true c8y api POST /service/dtm/definitions/properties --data "@$one" </dev/null ||
exit 1 # stop at the first rejected definition rather than reporting only the last
done < "$defs"

The device does not push the definition: device users do not hold the DTM roles, and declaring what a fleet may edit is a tenant decision anyway. The Parameters tab only renders fragments that match a definition, so without this step the values are still visible in the device’s inventory but not editable — an acceptable degraded mode.

A parameter is every point whose access permits writes, plus points that opt in with meta.parameter (read-only points then render readOnly: true, so the tab can display state next to the controls); meta.parameter = false opts a writable point out. Parameters are grouped into sets, one set = one DTM identifier = one twin fragment. This RFC’s default set name was <protocol>_parameters, which collides across device types; RFC 0005 replaced it with <device type, else protocol>_<group>_parameters and is the current rule. Datatype → JSON-schema type and integer bounds are automatic; meta.parameter.{title, description, min, max, enum, default, order} enrich the schema. The keys of a set are the point ids, unless a point names its own with meta.parameter.key (so firmwareVersion can be version in a firmware set: key = "firmware.version" names the set and the key at once); keys must be plain identifiers ([A-Za-z0-9_]; Cumulocity rejects dots in keys) and unique per set on a device — describe refuses both. The connector’s retained capability descriptor lists the keyed points (parameter_keys), so the flows know a key before the point samples: after a mapper restart, and for a write-only point.

Later addition: a point can also be a literal parameter with meta.parameter = { fragment = "<name>" }. Its value is then the fragment itself ("pump_speed": 42) and its DTM definition is a primitive jsonSchema, not an object with one property. A Parameters-tab edit carries the bare value ("pump_speed": 1500) and becomes a write-batch of one write. See openspec/specs/literal-parameters/spec.md.

Three places could own the definition; the config wins:

Source of the definitionVerdict
Connector TOML (this RFC)Already the single source of truth for points; offline, versionable, deterministic; the same meta table that drives flows drives the schema.
Cloud Fieldbus device type (RFC 0002)Only Modbus, and the import already lands in the TOML — so it feeds this path for free rather than replacing it. A device type could later gain a “parameter” flag that the import turns into meta.parameter.
Hand-written in the DTM UIWorks (the flows only need the identifier to match), but drifts from the config. Kept as the escape hatch.

2. Should the tedge-dot service react to the commands?

Section titled “2. Should the tedge-dot service react to the commands?”

To connector commands (te/device/<d>/ot/<protocol>/cmd/<verb>/<id>): yes, it already does, and this RFC adds write-batch there. To thin-edge/cloud commands (te/device/<d>///cmd/parameter_update/<id>, c8y_ParameterUpdate): no. The connector stays ignorant of thin-edge command types and cloud fragments; the bridge is flows, hot-reloaded and protocol-neutral, exactly like measurements and the existing ot_write bridge. Nor does the runtime publish the twin itself: that would be the driver’s first thin-edge-model output and every runtime (the Rust SDK, the C implementation) would have to replicate the set logic. What does belong in the runtime is what every requester would otherwise re-implement: writing N points as one ordered request with one result (write-batch), and echoing the point’s access in samples so a flow can recognise parameters without the TOML file.

3. How is the current value of a writable parameter reported, and what about output-only points?

Section titled “3. How is the current value of a writable parameter reported, and what about output-only points?”

ot-parameter-state publishes te/device/<d>///twin/<set> on change; the c8y mapper mirrors it into the managed object, which is exactly what the Parameters tab reads (the c8y_ParameterUpdate event path of the device-parameter service is not needed for that and is left out). Values come from:

  • readable parameters — every good sample, so the twin follows the device even when a value is changed locally on the HMI;
  • read/write parameters — additionally updated optimistically from an acknowledged write, then confirmed by the next sample;
  • write-only parameters (access = "write") — the last acknowledged write. They never produce samples, so their set is learned from nothing: they land in the default set (whose name the retained link status still qualifies with the device type — RFC 0005) — unless they name a key, whose entry in the capability descriptor (parameter_keys) names their sets.

Output-only points exist in every protocol (Modbus write-only registers behind FC06/16 on devices that reject reads of them, OPC UA nodes with AccessLevel = CurrentWrite, CANopen write-only objects). For those the honest answer is: the device cannot tell you the current state; you only know what you last commanded and that the protocol acknowledged it. The bridge reports exactly that, the DTM description says so (“write-only: shows the last value written”), and the value is absent (not null) until the first successful write after the mapper started, so the UI never shows an invented state. Persisting the last commanded value across mapper restarts is a follow-up (a retained state/<point> topic owned by the runtime, or the flow re-reading its own twin, which today’s loop protection forbids).

4. CLI (tedge-dot write) or MQTT commands?

Section titled “4. CLI (tedge-dot write) or MQTT commands?”

MQTT commands, always, while the service runs. tedge-dot write opens a second protocol session to the device: impossible on Modbus RTU (the serial port is exclusive), refused or disruptive on PLCs that cap Modbus TCP connections or OPC UA sessions, and invisible to the retained command state machine that flows and the cloud complete against. The CLI stays what it is — a commissioning and debugging tool for a stopped service. The parameter plugin’s “script per parameter set” model would have pushed writes through the CLI (see below), which is the main reason not to build on it for point writes.

tedge-parameter-plugin: owns the Cumulocity operation; the flows serve the OT children

Section titled “tedge-parameter-plugin: owns the Cumulocity operation; the flows serve the OT children”

tedge-parameter-plugin maps c8y_ParameterUpdate onto a parameter_update workflow (tedge-agent) whose prepare step picks the set name out of the operation and whose run step executes /usr/share/tedge/parameter-plugins/<set> set <json>; current values are whatever a script publishes to te/device/main///twin/<set>.

Two facts about thin-edge shape the coordination:

  1. The c8y mapper binds .template files by fragment name (get_template_name_by_operation_name picks the first template whose on_fragment matches, whatever workflow operation the device declared). Two templates for c8y_ParameterUpdate can therefore never coexist: a second one silently shadows the first for every device. An earlier revision of this prototype shipped its own template and hit exactly that.
  2. tedge-agent’s workflow engine subscribes to commands of its own entity only (EntityFilter::Entity(device_topic_id)), so a parameter_update command addressed to a child device is never picked up by the plugin’s workflow.

Hence the split: the plugin’s template is the single owner of the operation, the OT child devices advertise the plugin’s parameter_update command (published by ot-registration), the mapper symlinks the plugin’s template for them, and ot-command-forward / ot-command-result are the only handlers of that command on child devices. On the main device the plugin’s workflow and its script-per-set model keep working untouched — a natural home for gateway-level settings such as the connector poll_interval (a parameter-plugins/tedge_dot script issuing set-config; not part of this RFC). No change to the plugin is needed, and the “dynamic handler” problem does not arise: on children the set name is read from the c8y_ParameterUpdate_<set> marker by the flow.

main device (plugin)OT child devices (this RFC)
Operation templateplugin’s c8y_ParameterUpdate.templatethe same file, symlinked per child by the mapper
Command typeparameter_updateparameter_update
Handlertedge-agent workflow → set scriptflows → connector write-batch
Current valuesscript publishes the twinot-parameter-state from samples + acknowledged writes

Why the point writes are not routed through the plugin’s scripts instead: a script per set would push writes through tedge-dot write (a second protocol session, see Q4) or hand-rolled MQTT, and it has no notion of point state; on child devices it cannot run at all.

Contract additions (additive, SDK-provided)

Section titled “Contract additions (additive, SDK-provided)”
  • access in the sample envelope (contract §5): the point’s declared access, echoed like meta. No new topic, no conformance change.
  • write-batch verb (contract §6.4, command.schema.json): ordered, fail-fast, per-point results; advertised for every module with write (the conformance harness treats it as implied by write). Extra request fields (origin, c8y-mapper) are ignored by the connector and left on the retained init for the flows to correlate with.
  • meta.parameter — the first documented meta convention beyond the measurement hints; still uninterpreted by the connector (contract §5.2).
LayerWhatWhere
SDKparameter/set derivation from the config + DTM renderingimpl/rust/crates/sdk/src/descriptor.rs
SDK runtimeaccess in samples, write-batchimpl/rust/crates/sdk/src/runtime.rs
CLItedge-dot describe [<config-or-dir>...] [--config <config-or-dir>]... [--set] [--device] [--compact]impl/rust/src/main.rs, impl/c/src/main.c
Flowsot-parameter-state (new); ot-command-forward reshapes parameter_update, ot-command-result honours origin.command; ot-registration advertises parameter_updateflows/
c8y gluenone — the tedge-parameter-plugin’s template (installed by the cloud e2e image)
Testsoffline flow checks incl. the chain through shared mapper state (just test-flows); e2e: access in samples, batch semantics, and the flows-driven parameter round-trip on a cloud-free flows runner (just test-e2e modbus|opcua); cloud: DTM registration → fragment → operation → measurement (cloud/modbus/tests/parameters_c8y.robot)

A simplification pass removed an earlier retained point-descriptor topic and two dedicated parameter flows in favour of the access sample field and the existing command flows.

The C implementation (impl/c/) implements the same runtime pieces (access in samples, write-batch with the executing transition, and the management verbs with persist + live reload) and the same parameter derivation and DTM rendering (impl/c/sdk/src/descriptor.c, tedge-dot describe), so the flows, the Cumulocity glue and the tenant admin’s registration step work unchanged with either binary. The C build runs the same Robot e2e suites (just test-e2e-c), the same cloud suites (just test-cloud-c, which builds the C connector into the thin-edge demo image) and the same conformance suite (just conformance-c) as the Rust build; just c-describe-parity additionally asserts that both binaries render the same definitions (compared parsed, since key order differs) for every connector config in the repo.

The e2e stacks gained a flows service: thin-edge from the main channel running this repo’s flows as a user-defined mapper (tedge-mapper ot) against the stack’s broker, so the full device-side chain — registration, command bridge, parameter bridge, twin — is exercised without a cloud. It needs a thin-edge build with user-defined mappers (2.0.2+ dev), which is also the reason the demo image (2.0.1) only runs the flows inside the c8y mapper.

Parameters tab ─ c8y_ParameterUpdate ─▶ c8y mapper (plugin's template) ─▶ te/device/plc1///cmd/parameter_update/<id> {operation:{...}}
                                                            │ ot-command-forward (keys are point ids)
                                                            ▼
                                        te/device/plc1/ot/modbus/cmd/write-batch/ot--<id> {writes:[...], origin:{command:...}}
                                                            │ tedge-dot: write, write, ... (fail-fast)
                                                            ▼
                                        ... {status:successful, results:[...]}
                          ┌─────────────────────────────────┴──────────────────────────────┐
                          │ ot-command-result (origin.command)                             │ ot-parameter-state
                          ▼                                                                ▼
   te/device/plc1///cmd/parameter_update/<id> {successful, c8y-mapper}   te/device/plc1///twin/<set> {...}
                          │ c8y mapper                                                     │ c8y mapper
                          ▼                                                                ▼
                 operation SUCCESSFUL                                            managed object fragment (UI refreshes)
  • Persist last-commanded values of write-only parameters across mapper restarts (see Q3).
  • One DTM identifier is tenant-wide: heterogeneous fleets must name sets per device type — settled by RFC 0005: a device declares its type (or inherits it from its point library) and the set names are derived from it. The Cloud Fieldbus import (RFC 0002) can fill that type in from the device type it already reads.
  • write-batch is sequential and non-atomic; a Modbus FC16 fast path for contiguous registers is a connector-local optimisation with the same result shape.
  • The twin is republished on every value change of a readable parameter (retained, one inventory update each). Noisy parameters are better modelled as measurements than as parameters.
  • Cumulocity’s device-parameter service and DTM are opt-in microservices; the twin fragment is still published (and inventory-visible) on tenants without them.
  • A c8y_ParameterUpdate event (Cumulocity’s audit trail for parameter changes) could be added as a tiny flow on top of the twin later; it is not needed for the UI.